Part Number Hot Search : 
EPM7192 UG30APT 120EE CY2DL814 120EE A80BD 3100B F1608
Product Description
Full Text Search
 

To Download DCS80-13E Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 LABORATORY
DCS Series
1000-3000 WATTS PROGRAMMABLE DC SUPPLY Features
* * * * * High power density Remote voltage sense & remote programming Wide range of output voltages High programming resolution with ethernet interface Remote control
Specifications
INPUT
Input voltage 1KW: 200-250VAC, single phase; 100-132VAC single phase, internal jumper selectable (see M1 option) 1.2KW: 200-250VAC, single phase; 100132VAC single phase, internal jumper selectable (see M1 option) 3KW: 190-250VAC, three phase; 200-250VAC, single phase (Note: Max.power output of 3KW supplies must be limited to 2.5KW for single phase input) 47-63Hz for both single and three phase input 1KW: 15A typ at 115VAC, 8A typ at 230VAC, 1.2KW: 18A typ at 115VAC, 9A typ at 230VAC, 3KW: 20A typ at 230VAC single phase, 14A typ at 230VAC three phase Line current is lower than full load peak value during turn-on or power application after restart
OPERATING
Efficiency Remote sense See table The maximum allowed sense line drop is 4V per line (2V on the DCS 8 and 10V 1KW and 1.2KW models and 1V/ line for all 3KW models) External jumper via rear panel connectors J3. Crowbar type adjustable from 5-110% Protection rated output using front panel control (local or remote program selectable via J3 jumper) Linearity: +/-1% Accuracy: +/-5% LabVIEW(R) driver for M9C/M85 (Contact Powerbox) CE Mark on all models, FCC Part 15 Class A UL1012 and CSA 22.2 #220 (1 and 1.2 KW only)
Remote programming Overvoltage protection
Frequency Current
Remote analog programming Software Regulatory compliance
Soft start
ENVIRONMENTAL
Operating temperature Storage temperature Humidity range Cooling 0C to 50 (No De-rating) -40C to 85C 0-80% RH, non condensing Internal fan with over-temperature protection
Options and Accessories
INPUT VOLTAGE OPTIONS
M1 M9C M13 Zero to rated output Zero to rated output See table Voltage: 0.1% Current: 0.1% Typically recovers in < 1ms to 1% of steady-state output voltage (within 1% of Vmax) for 70-100% or 100-70% load change. 500 s typical +/-0.05% of maximum voltage or current over 8 hours after 30 minute warm-up time at fixed line, load and temperature 0.02%/C of maximum output voltage 0.03%/C of maximum output current M85 M102 M32 M33 M51A Factory configured for 115VAC input (1 and 1.2kW only) Internal IEEE-488/RS 232 interface Locking shafts (front panel potentiometers) Master/slave cable configured for two or more units Replace input connector with terminal block (3kW only) Isolated analog programming control of V/I/OVP and isolated V/I monitor outputs up to 500V relative to the supply's return line Multichannel slave interface Front panel binding posts for 1kw or 1.2 kW, Models 30A, 100V. Not compatible with M9C, M85, M130, M131, M133, M135, M136 LXI compliant 10/100 Base T Ethernet remote control master interface; includes web server for direct control of power supply via web browser (MS Internet Explorer 6.0 or later) 16-bit slave interface option for use with a M130 master (3 ft. control cable included) Output disconnect and polarity reversal controlled via SCPI commands. Limited to 1k or 1.2 kW, 300V, 60A M130 & M133 combination M131 & M133 combination Rack slide kit (3kW)
REMOTE INTERFACE OPTIONS
OUTPUT
Voltage adjustment Current adjustment Ripple & Noise Regulation (Line or Load) Transient response
Stability
M130
Temperature Coefficient
M131 M133
M135 M136 105-330-26
484
LABORATORY
DCS Series
1000-3000 WATTS PROGRAMMABLE DC SUPPLY
CONSTANT CURRENT MODE* MODEL COMBINED REGULATION LINE AND LOAD % TEMP. COEFF. VOLTAGE %/C (TYP) PROGRAMMING INPUT CURRENT, A CASE VOLTAGE CONSTANTS CURRENT NORMAL MODE DRIFT % % EFFICIENCY IO MAX 230V 208V % (TYP) SINGLE THREE OHMS/A V/A (TYP) PHASE PHASE
RIPPLE (RMS)
DCS 8-140E 0.2 180 0.03 0.05 DCS 10-120E 0.2 153 0.03 0.05 DCS 20-60E 0.2 30 0.03 0.05 DCS 33-36E 0.2 11 0.03 0.05 DCS 40-30E 0.2 9 0.03 0.05 DCS 50-24E 0.2 8.5 0.03 0.05 DCS 60-20E 0.2 6.6 0.03 0.05 DCS 80-15E 0.2 6 0.03 0.05 DCS 100-12E 0.2 3.6 0.03 0.05 DCS 150-8E 0.2 2.3 0.03 0.05 DCS 300-4E 0.2 1.2 0.03 0.05 * Typical resolution is 0.02% **RMS ripple from 20Hz to 300kHz ***Consult factory Dimension: 1RU or 44mm (H) x 482mm (W) x 444mm (D) ; Weight: 8.6kg86
35.7 41.7 83.3 138.9 166.7 208.3 250 333.3 416.7 625 1250
0-10V= 0-100% Io or 0-5V= 0-100% Io
9 9 9 9 9 9 9 9 9 9 9
N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
82 82 82 84 84 84 85 85 85 85 85
I I I I I I I I I I I
DSC 3kW Series
TEMP. COMBINED CONSTANT VOLTAGE MODE* COEFF. VOLTAGE REGULATION DRIFT % CURRENT RIPPLE NOISE TRANSIENT VOLTAGE LINE AND VMAX VOLTAGE ADC @ (RMS)** (P-P) RESPONSE %/C LOAD % (TYP) VDC 50C (TYP.) (TYP) TIME (TYP) (TYP) OUTPUT POWER PROGRAMMING CONSTANTS VOLTAGE MODES OHMS/V V/V
MODEL
DCS 8-350E DCS 12-250E DCS 20-150E DCS 40-75E DCS 55-55E DCS 60-50E DCS 80-37E DCS 150-20E
0-8 0-12 0-20 0-40 0-55 0-60 0-80 0-150
0-350 0-250 0-150 0-75 0-55 0-50 0-37 0-20
0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2
15mV 10mV 10mV 20mV 20mV 20mV 20mV 30mV
100mV 100mV 100mV 100mV 100mV 100mV 100mV 200mV
1000 1000 1000 1000 1000 1000 1000 1000
s s s s s s s s
0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02
0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05
625 416.7 250 125 90.9 83 62.5 33.3
0-10V = 0-100% Vo or 0-5V = 0-100% Vo
CONSTANT CURRENT MODE* MODEL COMBINED REGULATION LINE AND LOAD %
PROGRAMMING TEMP. VOLTAGE CONSTANTS CURRENT COEFF. MODE DRIFT % % VOLTAGE I MAX O RIPPLE %/C OHMS/A V/A (TYP) (RMS) (TYP)
INPUT CURRENT, A NORMAL 230V SINGLE PHASE 208V THREE PHASE
CASE EFFICIENCY % (TYP)
DCS 8-350E 0.2 870 0.03 0.05 DCS 12-250E 0.2 400 0.03 0.05 DCS 20-150E 0.2 100 0.03 0.05 DCS 40-75E 0.2 75 0.03 0.05 DCS 55-55E 0.2 40 0.03 0.05 DCS 60-50E 0.2 33 0.03 0.05 DCS 80-37E 0.2 20 0.03 0.05 DCS 150-20E 0.2 10 0.03 0.05 * Typical resolution is 0.02% **RMS ripple from 20Hz to 300kHz ***Consult factory Dimension: 2RU or 88mm (H) x 482mm (W) x 444mm (D) ; Weight: 15kg
14.7 20 33.3 66.7 90.9 100 135 250
0-10V= 0-100% I0 or 0-5V= 0-100% I0
24 26 26 26 26 26 26 26
13 14 14 14 14 14 14 14
82 82 82 86 82 86 86 86
II II II II II II II II
486
LABORATORY
DCS Series
1000-3000 WATTS PROGRAMMABLE DC SUPPLY DSC 1kW Series
CONSTANT COMBINED REGULATION CURRENT LINE AND VOLTAGE RIPPLE ADC @ LOAD % VDC (RMS)** (TYP.) 50C OUTPUT POWER PROGRAMMING CONSTANTS TEMP. VOLTAGE MODES COEFF. VOLTAGE DRIFT % NOISE TRANSIENT VOLTAGE VMAX (P-P) RESPONSE OHMS/V V/V %/C (TYP) (TYP) TIME (TYP) (TYP) VOLTAGE MODE*
MODEL
DCS 8-125E DCS 10-100E DCS 20-50E DCS 33-33E DCS 40-25E DCS 50-20E DCS 60-18E DCS 80-13E DCS 100-10E DCS 150-7E DCS 300-3.5E DCS 600-1.7E
0-8 0-10 0-20 0-33 0-40 0-50 0-60 0-80 0-100 0-150 0-300 0-600
0-125 0-100 0-50 0-33 0-25 0-20 0-18 0-13 0-10 0-7 0-3.5 0-1.7
0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2
4mV 4mV 4mV 4mV 4mV 4mV 4mV 4mV 6mV 12mV 20mV 50mV
60mV 60mV 60mV 60mV 60mV 60mV 60mV 60mV 60mV 160mV 200mV 300mV
500 500 500 500 500 500 500 500 500 500 500 500
s s s s s s s s s s s s
0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02
0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05
625 500 250 151.5 125 100 83 62.5 50 33.3 16.67 8.33
0-10V = 0-100% Vo or 0-5V = 0-100% Vo
CONSTANT CURRENT MODE* MODEL COMBINED REGULATION LINE AND LOAD %
PROGRAMMING TEMP. VOLTAGE CONSTANTS CURRENT COEFF. MODE DRIFT % % VOLTAGE IO MAX RIPPLE %/C OHMS/A V/A (TYP) (RMS) (TYP)
INPUT CURRENT, A NORMAL 230V SINGLE PHASE 208V THREE PHASE
CASE EFFICIENCY % (TYP)
DCS 8-125E 0.2 160 0.03 0.05 40 DCS 10-100E 0.2 128 0.03 0.05 50 DCS 20-50E 0.2 25 0.03 0.05 100 DCS 33-33E 0.2 10 0.03 0.05 151.5 DCS 40-25E 0.2 7 0.03 0.05 200 DCS 50-20E 0.2 7 0.03 0.05 250 DCS 60-18E 0.2 6 0.03 0.05 277.8 DCS 80-13E 0.2 4 0.03 0.05 384.6 DCS 100-10E 0.2 3 0.03 0.05 500 DCS 150-7E 0.2 2 0.03 0.05 714.3 DCS 300-3.5E 0.2 1 0.03 0.05 1428.6 DCS 600-1.7E 0.2 1 0.03 0.05 2941.2 * Typical resolution is 0.02% **RMS ripple from 20Hz to 300kHz ***Consult factory Dimension: 1RU or 44mm (H) x 482mm (W) x 444mm (D) ; Weight: 8.6kg
0-10V= 0-100% Io or 0-5V= 0-100% Io
8 8 8 8 8 8 8 8 8 8 8
N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
82 82 82 84 84 84 86 86 86 86 86
I I I I I I I I I I I
9.5
N/A
86
***
DSC 1.2kW Series
OUTPUT POWER MODEL VOLTAGE CURRENT VDC ADC @ 50C COMBINED REGULATION LINE AND LOAD % CONSTANT VOLTAGE MODE* RIPPLE (RMS)** (TYP.) NOISE (P-P) (TYP) PROGRAMMING CONSTANTS TEMP. VOLTAGE MODES COEFF. VOLTAGE DRIFT % VOLTAGE TRANSIENT VMAX %/C (TYP) RESPONSE OHMS/V V/V (TYP) TIME (TYP)
DCS 8-140E DCS 10-120E DCS 20-60E DCS 33-36E DCS 40-30E DCS 50-24E DCS 60-20E DCS 80-15E DCS 100-12E DCS 150-8E DCS 300-4E
0-8 0-10 0-20 0-33 0-40 0-50 0-60 0-80 0-100 0-150 0-300
0-140 0-120 0-60 0-36 0-30 0-24 0-20 0-15 0-12 0-8 0-4
0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2
5mV 5mV 5mV 5mV 5mV 5mV 5mV 5mV 10mV 15mV 25mV
60mV 60mV 60mV 60mV 60mV 60mV 60mV 60mV 60mV 160mV 200mV
500 500 500 500 500 500 500 500 500 500 500
s s s s s s s s s s s
0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02
0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05
625 500 250 151.5 125 100 83 62.5 50 33.3 16.67
0-10V = 0-100% Vo or 0-5V = 0-100% Vo
Your dependable power partner - www.powerbox.com.au
485
LABORATORY
DCS Series
1000-3000 WATTS PROGRAMMABLE DC SUPPLY Options & Accesssories
INPUT VOLTAGE OPTIONS
M1 M9C M13 M32 M33 M51A M102 M85 M130 M131 M133 M135 M136 Factory configured for 115 VAC input (1 and 1.2 kW only) 1 2 3 4 5 6 7 8 9 10 11 12 13
J3 PROGRAM AND SENSE
90-250 VAC Remote Shutdown 14 Shutdown Return OVP Program Remote/Local Status Indicator Mode Status Indicator Ground 0-5V Current Monitor Voltage Control Voltage Program Input Current Program Unit Current Control Return Sense POS Sense (8-100V Models Only 15 16 17 18 19 20 21 22 23 24 25 TTL Shutdown +12 VDC 1 mACurrent Source (OVP) OVP Indicator Thermal S/DN Status 0-5V Voltage Monitor Remote Voltage Select 1 mA Current Source (V) 1 mA Current Source (I) Remote Current Select Return POS Output (8-100V Models Only)
REMOTE INTERFACE OPTIONS
Internal IEEE-488/RS 232 interface (Supports only 12-bit slaves) Locking shafts (front panel potentiometers) Master/slave cable configured for two or more units Replace input connector with terminal block(3 kW only) Isolated analog programming control Front Panel Binding Posts (1 kW and 1.2 kW only?30A) 12-bit slave interface Ethernet/RS232 Interface (Supports both 12- & 16-bit slaves) 16-bit slave interface Output disconnect and polarity reversal relays* Output disconnect and polarity reversal relays** Output disconnect and polarity reversal relays***
105-330-26 Rack slide kit (3 kW only) * Requires M9C ** Includes option M130 ***Includes option M131
Technical Illustrations
1KW AND 1.2KW 3KW
Your dependable power partner - www.powerbox.com.au
487


▲Up To Search▲   

 
Price & Availability of DCS80-13E

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X